Product Overview & Applications

The RB 1700 uses a spring-loaded diaphragm and balanced valve to regulate downstream gas pressure without an external power supply. It is intended for commercial loads, burners, ovens, boilers and secondary distribution.

Technical Specifications

Maximum inlet pressure19 bar
Outlet range0.12–2.5 bar; selected spring and version
ConnectionsThreaded ¾ or 1 in; flanged DN25
Gas temperature−20°C to +60°C
BodyDuctile iron

Specifications refer to the cited product literature. Final ratings and options follow the selected model and ordered configuration.

Features & Configuration

  • Optional over-pressure or combined over/under-pressure shut-off.
  • Safety trip setting adjustable separately from the regulator.
  • Monitor configuration available.

Selection & Quotation

For selection, specify gas type, minimum and maximum inlet pressure, required outlet pressure, minimum and maximum flow, connection size and pressure rating, and any shut-off settings.